Standard Damper Actuators
Standard Damper Actuators
The F30A series is designed for precise control of air volume and direction in commercial and industrial ventilation systems. As non-spring return actuators, they hold their position when power is removed, making them suited to modulating and on/off duties where a defined fail-safe position isn't required. Three variants are available — standard, low noise, and fast running — sharing a common mounting arrangement and control platform, so specifiers can select on performance without changing installation approach.

Choosing Your Variant
Use this to identify which variant suits the application, then see the full specification for each below.
| Standard | Low Noise | Fast Running | |
|---|---|---|---|
| Torque | 2–40 Nm | 2–10 Nm | 5–16 Nm |
| Running time | 35–100 s | 75–150 s | 2.5–8 s |
| Noise level | ≤45 dB | ≤35 dB | 55–60 dB |
| Life cycle | ≥70,000 | ≥70,000 | ≥30,000 |
| Certification | CE, UKCA, UL, RoHS | CE, UKCA, RoHS | CE, UKCA, RoHS |
| Best for | General HVAC | Noise-sensitive spaces | Rapid response |
F30A Series Standard Damper Actuator
The core actuator for everyday HVAC applications, covering six torque ratings and damper areas up to 8 m².
Find out more technical details about our F30A
Torque and Running Time
| Torque | Damper area | Running time | Weight |
|---|---|---|---|
| 2 Nm | 0.5 m² | 35 s | 0.5 kg |
| 5 Nm | 1 m² | 45 s | 0.5 kg |
| 10 Nm | 2 m² | 60 s | 0.9 kg |
| 20 Nm | 4 m² | 75 s | 0.9 kg |
| 30 Nm | 6 m² | 75 s | 1.4 kg |
| 40 Nm | 8 m² | 100 s | 1.4 kg |
Specification
- Supply voltage: AC/DC 24 V (19.2–28.8 V) or AC 230 V (85–265 V), 50/60 Hz
- Control: 2/3 point, or modulating 0(2)–10 V / 0(4)–20 mA
- Power consumption: 1.5–5 W in operation, 0.7–1 W at rest
- Angle of rotation: 0–90° (max 93°), L/R switchable
- Position feedback: None or 2 SPDT
- Protection: IP54, class II/III
- Ambient: −30 to +50 °C, 5–95% RH
- Life cycle: ≥70,000
- Spindle: 8–18 mm (2/5 Nm) · 12–26.7 mm (10–40 Nm)
- Certification: CE, UKCA, UL, RoHS
Order Code
F30A – [torque] [control] [voltage] – [accessory]
Control: D = 2/3 point, M = modulating. Voltage: 24 = AC/DC 24 V, 230 = AC 85–265 V. Accessory: S = auxiliary switches.
Example: F30A-10M24-S — 10 Nm, modulating, 24 V, with auxiliary switches.
F30A Series Low Noise Damper Actuator
Where acoustic performance matters — offices, hotels, healthcare, education — this variant runs at ≤35 dB, a 10 dB reduction from the standard unit.
Find out more technical details about our F30A-L

Torque and Running Time
| Torque | Damper area | Running time | Weight |
|---|---|---|---|
| 2 Nm | 0.5 m² | 75 s | 0.5 kg |
| 5 Nm | 1 m² | 150 s | 0.5 kg |
| 10 Nm | 2 m² | 150 s | 0.9 kg |
Specification
- Noise level: ≤35 dB
- Supply voltage: AC/DC 24 V or AC 230 V, 50/60 Hz
- Control: 2/3 point, or modulating 0(2)–10 V / 0(4)–20 mA
- Power consumption: 1.5–2.5 W in operation
- Angle of rotation: 0–90° (max 93°), L/R switchable
- Position feedback: None or 2 SPDT
- Protection: IP54, class II/III
- Ambient: −30 to +50 °C
- Life cycle: ≥70,000
- Certification: CE, UKCA, RoHS
Order Code
Suffix L denotes low noise; SL denotes low noise with auxiliary switches.
Example: F30A-5D24-L — 5 Nm, 2/3 point, 24 V, low noise.
Note: Running times are roughly double the standard variant. Confirm this suits the control strategy before specifying.
F30A Series Fast Running Damper Actuator
Fast-running actuators are designed for HVAC applications where the damper must reach its commanded position significantly faster than with a conventional actuator.
They provide rapid and accurate positioning for applications requiring quick airflow adjustment, pressure control or system response, while retaining the same flexible control options available across the standard actuator range.
Find out more technical details about our F30A-Q

Torque and Running Time
| Torque | Damper area | Running time | Weight |
|---|---|---|---|
| 5 Nm | 1 m² | 2.5–3.5 s | 1.0 kg |
| 10 Nm | 2 m² | 4–5 s | 1.0 kg |
| 16 Nm | 4 m² | 7–8 s | 1.0 kg |
Specification
- Running time: 2.5–8 s depending on torque
- Supply voltage: AC/DC 24 V or AC 230 V, 50/60 Hz
- Control: 2/3 point, or modulating 0(2)–10 V / 0(4)–20 mA
- Power consumption: 15 W in operation, 2 W at rest
- Noise level: 55–60 dB
- Angle of rotation: 0–90° (max 93°), L/R switchable
- Protection: IP54, class II/III
- Ambient: −30 to +50 °C
- Life cycle: ≥30,000
- Spindle: 12–26.7 mm
- Certification: CE, UKCA, RoHS
Order Code
Suffix Q denotes fast running; SQ denotes fast running with auxiliary switches.
Example: F30A-16D24-Q — 16 Nm, 2/3 point, 24 V, fast running.
Note: Higher speed carries trade-offs — 15 W draw against 1.5–5 W for the standard unit, 55–60 dB against ≤45 dB, and a ≥30,000 cycle life against ≥70,000. Size the supply accordingly.
Control Signals and Wiring
All modulating F30A actuators use an onboard SW1 dial switch to select input signal type and feedback range, so a single model covers several control configurations.
| Input signal | Feedback | Input resistance |
|---|---|---|
| DC 0–10 V | DC 0–10 V | 150 kΩ |
| DC 2–10 V | DC 2–10 V | 150 kΩ |
| DC 0–20 mA | DC 0–10 V | 500 Ω |
| DC 4–20 mA | DC 2–10 V | 500 Ω |